Linear Bar Grille with Removable Core – 600 × 150
Available from Stock
Description
A clean, architectural linear bar grille with removable core, designed for wall-mounted supply air applications.
The quick-release removable core provides easy access behind the grille for installation, cleaning and maintenance, while the fixed 0° blades provide a straight-through air pattern.
Ordering & Sizing
Nominal Size: 600 × 150mm
Actual Neck Size: 590 × 140mm
Overall Face Size: 630 × 180mm
When ordering: Grille sizes are based on the nominal neck size. The actual neck is 10mm smaller than nominal to provide installation clearance.
Features
- Quick-release removable core
- Fixed 0° linear blades
- 12.5mm blade pitch
- 2.5mm thick blades
- Extruded aluminium construction
- White powder-coated finish
- Suitable for wall mounting
- Designed for supply air applications
- Concealed fixing arrangement
- Suitable for residential and commercial HVAC systems
Specifications
| Specification | Details |
|---|---|
| Product Code | RCBG246 |
| Nominal Neck Size | 600 × 150mm |
| Actual Neck Size | 590 × 140mm |
| Overall Face Size | 630 × 180mm |
| Grille Depth | 50mm |
| Flange Width | 25mm |
| Construction | Extruded aluminium |
| Blade Thickness | 2.5mm |
| Blade Pitch | 12.5mm |
| Blade Deflection | 0° |
| Finish | White powder coat |
| Removable Core | Yes |
| Dampenable at Grille Face | No |
| Application | Supply air |
| Mounting | Wall |
Airflow Performance
For the 600 × 150 RCBG246, the manufacturer's published performance data is:
| Face Velocity | Airflow | Throw | Pressure Drop | NC |
|---|---|---|---|---|
| 1 m/s | 70 L/s | 2.0 m | 1 Pa | <15 |
| 2 m/s | 140 L/s | 3.2 m | 4 Pa | <15 |
| 3 m/s | 211 L/s | 4.4 m | 10 Pa | <15 |
| 4 m/s | 281 L/s | 5.6 m | 17 Pa | 15 |
Airflow at 2 m/s: 140 L/s
For typical supply-air sizing, 140 L/s at 2 m/s provides a useful design reference. Actual system performance will depend on the ductwork, available pressure and installation.
Installation Note
The grille has fixed 0° blades and does not provide airflow adjustment at the grille face. Where airflow balancing is required, a suitable balancing damper should be installed within the duct system.